Ventilation (Air Changes) Calculator

Calculate required ventilation airflow from room dimensions and air changes per hour.

Required ventilation
191 CFM
Room volume 54 m³ × 6 ACH ÷ 3600 = 0.09 m³/s
Flow (m³/h)
324
Flow (L/s)
90
Room volume
54 m³

Estimates for planning purposes only. Verify against local ventilation codes and consult a qualified HVAC professional before installation.

How it works

  1. 1Enter the room’s length, width, and height in metres or feet.
  2. 2Select the room type to apply its recommended air changes per hour (ACH).
  3. 3The calculator multiplies volume × ACH ÷ 3600 to give airflow in m³/s, m³/h, L/s, and CFM.

Use cases

  • Sizing an extract fan or MVHR unit for a bathroom or kitchen.
  • Verifying an office meets minimum fresh-air ventilation requirements.
  • Estimating duct and fan capacity for a whole-house strategy.

Frequently asked questions

What does air changes per hour (ACH) mean?

ACH is how many times the room’s air volume is replaced per hour. A 40 m³ bedroom at 5 ACH needs 200 m³/h (≈ 118 CFM).

How is required airflow calculated?

Q (m³/s) = volume × ACH ÷ 3600. A 54 m³ kitchen at 10 ACH needs 0.15 m³/s = 540 m³/h ≈ 318 CFM.

Which standard defines ACH values?

ASHRAE 62.1 (commercial) and 62.2 (residential) are widely used. Local codes may set higher minimums — check the authority having jurisdiction.